SmartLine

Conventional control panels with 2 zones or 4 zones expandable to 36

The SmartLine conventional fire-detection control panel series offers a 2 zone non-expandable model (SmartLine020-2), a 4 zone model expandable to 20 zones (SmartLine020-4) and a 4 zone model expandable to 36 zones (SmartLine036). The extreme compactness, trouble-free installation, uncomplicated programming procedures and simple end-user operation make this highly competitive control panel ideal for all small and medium applications, especially those applications where fast installation and programming are among the most important aspects of the system. The numerous functions (timers, equational logic, etc.), extensive flexibility (automatic output balancing, multifunction inputs, customizable outputs, gas function integration, etc.), and innovative connectivity capabilities (RS485 BUS for power supply stations, Internet connection, etc.), provide the tranquillity of knowing for sure that this powerful tool is capable of satisfying every need of every type of installation. SmartLine control panels have supervised outputs (one on the motherboard and one on each added expansion) for the activation of audio-visual signalling devices, a customizable relay output, fault signaling outputs and two 24V outputs (one constant and one interruptible by installer-defined conditions). Additionally, each detection zone provides a terminal which can be configured as: open-collector output (activated by programmable conditions), supervised input, or Gas 4-20mA detector interface. System information is provided through the graphic display and LEDs on the control panel frontplate. The RS485 BUS supports 4 remote repeater panels (SmartLetUSee/LCD-Lite). These repeater panels replicate all the fire alarm system data and allow users to access and control the system in accordance with their authorized access level. The BUS also supports two power-supply stations which can be connected in such a way as to allow supervision of their functionality and activation/deactivation of their output power during predefined conditions. Programming the system from the control panel is straightforward and trouble-free thanks to the easy-to-follow instructions on the display. The system can also be programmed by means of the SmartLeague software application. This intuitive programming software greatly simplifies the programming procedure. The SmartLAN/485 board allows the control panel to connect to an Ethernet network for remote access via the Internet. Once the remote connection has been established, it is possible to modify the configuration parameters, upload/download programming data and/or manage the system by means of the supervisory software based on SmartLook graphic maps.

 

Features

 

  • Conventional fire-detection control panel.
  • Available with 2 zones, 4 zones expandable to 20, 4 zones expandable to 36
  • Certified EN54 / EN54-2
  • Certified EN12094-1 (Fire extinction)
  • Supports up to 32 devices per zone
  • Manages SmartLetLoose/ONE Fire Extinction board (Function EN12094-1 Approved)
  • 1 supervised alarm output (NAC)
  • 1 output for communicator/dialler activation
  • 1 dry-contact alarm output
  • 1 dry-contact fault output
  • 1 ancillary power supply output
  • 1 interruptible power supply output
  • 1 additional terminal per zone configurable as: open-collector output, supervised input, Gas detector input with 4-20mA interface
  • Battery shutdown relay for deep discharge conditions
  • Backlit graphic display for easy management of Installer/User interface
  • Navigation keys for easy access to graphic display functions
  • Fast keys (Silence, Reset, Evacuate, Investigate)
  • RS485 BUS for the connection of Repeater panels and Power supply stations (SmartLevel)
  • Buzzer (provides audible signals)
  • 8 Timers
  • 8 logical equations
  • Automatic balancing of individual detector lines
  • RS232 connector for system programming from a PC
  • Programming software
  • Easy system programming from the control panel
  • Access key for Level 2 functions (EN54 compliant)
  • Thermal probe for battery optimization
  • Battery efficiency test
  • Extensive application of SMD reflux technology for higher reliability
  • Metal enclosure
  • Mains power supply 230Vac
  • Switching power supply/battery charger 1.4A @ 27.6Vdc (for SmartLine020) or 4A @ 27.6Vdc (for SmartLine036)
  • Battery housing for two 7Ah - 12V batteries (for SmartLine020) or two 17Ah - 12V batteries (for SmartLine036)
  • Dimensions (HxWxD for SmartLine020): 325x325x80mm - (HxWxD for SmartLine036): 497x380x87mm
  • Weight (without batteries): SmartLine020 = 3Kg; SmartLine036 = 6Kg
Iris Series

Iris series detectors maintain the ease-of-use of conventional detectors, yet are capable of providing a series of technical solutions that until today were provided by only the most sophisticated addressable analogue systems. As a result of advanced technologies based on new-generation microprocessors, these detectors implement a set of sophisticated algorithms capable of ensuring unequalled reliability and a high immunity to false alarms. The ground-breaking Versa++ technology incorporated in IRIS series detectors allows you to configure individual detectors to suit their specific environments and, when used in conjunction with the EITK1000 kit, to connect directly to the detector line for a complete diagnosis of each detector and thus test its operating capacity, verify its real-time values, view the contamination level in the optical smoke chamber and change its sensitivity and operating mode. Each detector has a non-volatile memory which allows you to view the smoke and temperature levels measured in the period prior to the last alarm detected. These detectors have passed - with flying colours - all the tests taken at the LPCB test facility, the prestigious English certification service.

EB0010 Detector base

EB0010 Detector base

Detector base accommodates IRIS and ENEA series detectors, equipped with short-circuit plate which ensures continuity in the event of removal of the detector from the line.
EB0020 Relay base

EB0020 Relay base

Relay base with a single relay which activates when the detector senses an alarm. The relay base allows you to interface the detector with intrusion control panels in domestic applications.
ID100 Optical smoke detector

ID100 Optical smoke detector

The ID100 optical smoke detector is based on the Tyndall effect (diffusion of light) and provides first-rate early warning in the event of fire. It offers wide-spectrum detection of smoke particles generated by the majority of fires. The newly designed optical chamber with sealed upper-part and 500 μm holes diameter mesh insect screen ensure high immunity to false alarms. The sensitivity can be configured to suit a wide range of applications (sensitivity configurable as: 0.08dB/m; 0.10dB/m; 0.12dB/m; 0.15dB/m).
ID200 Heat detector

ID200 Heat detector

The response characteristics of the ID200 heat detector have been carefully set in A1R mode (fixed threshold at 58°C with thermovelocimetric detection). However, it can be set (by means of EDRV1000 driver) to operate in B mode (fixed threshold at 72°C); in A2S mode (fixed threshold at 58°C); in BR mode (fixed threshold at 72°C with thermovelocimetric detection). As a result of such flexibility, this detector is useful in places where the environment is dusty or smoky and the risk of false alarms is high.
ID300 Smoke and Heat detector

ID300 Smoke and Heat detector

The ID300 smoke and heat detector has new smoke and temperature sensing technologies. As a result, this improved â€"reliability detector responds well to all types of fires (especially to fast burning blazing fires involving inflammable liquids, which produce a limited amount of smoke) and is highly immune to false alarms. The ID300 can be set to the sensitivity mode which best suits the application (by means of EDRV1000 driver).
IC0020 Manual callpoint

IC0020 Manual callpoint

  • Manual callpoint with resettable element operated by plastic key (included)
  • Warning flag and LED confirmation of activation
  • Selectable resistence
IC0010E Manual callpoint for outdoor installation

IC0010E Manual callpoint for outdoor installation

  • Manual callpoint with resettable element. Weatherproof to IP67, suitable for outdoor installation
IS0010RE

IS0010RE conventional sounder

These audible signalling devices operate at 17 to 60 Vdc. Protection rating IP65. Complete with mounting base. They provide 32 tones configured by means of a DIP switch. The volume is easily adjusted using the internal trimmer.
IS0020RE

IS0020RE conventional sounder/beacon unit in red enclosure

IS0020RE conventional sounder/beacon unit in red enclosure. These audible signalling devices operate at 17 to 60 Vdc. Protection rating IP65. Complete with mounting base. They provide 32 tones configured by means of a DIP switch. The volume is easily adjusted using the internal trimmer.
SmartLetUSee/LCD-Lite

SmartLetUSee/LCD-Lite

Remote repeater panel equipped with display and user-interface keypad (up to 4 for each control panel)
SmartLetLoose/ONE

SmartLetLoose/ONE

Fire extinction board. Provides control panel with a Fire Extinction Gas control capabilities. Certified CPD- EN12094-1.
SmartLevel

SmartLevel

Power-supply station. Connectable to the RS485 BUS (for supervision and management of the control panel power-supply-station outputs.
SmartLine/8Z

SmartLine/8Z

8 zone expansion board equipped with an additional supervised output.
SmartLAN/485

SmartLAN/485

Ethernet connection board. Allows the control panel to connect to an Ethernet network for remote for programming and monitoring via the Internet using SmartLook graphic maps.